SL3 Series Project-Specific Surge Current Selection Chart

Step 1 : SPD Product Selection Guide

Step 2 : Project-Specific Surge Current Selection Chart

Step 3 : Application Guide

Service Entrance Section (SES), Main Panel

Tested Surge Current Capacity per Mode (x2 per Phase)

Source Current RatingSingle SESMultiple SES*
3000 A (and above)300 kA200 kA
2500 A250 kA200 kA
2000 A200 kA150 kA
1600 A150 kA125 kA
1000 A – 1200 A125 kA125 kA
800 A100 kA80 kA
400 A – 600 A80 kA50 kA
200 A50 kA50 kA
   Click on the applicable surge current rating (above) for project-specific model numbers and application guides.


*  Multiple Service Entrances to be understood as one feed from a utility substation feeding multiple (i.e., more than one) utility transformers and/or utility meters for their respective Service Entrance sections.